Get in touch Panel login

Hospitals and Healthcare

Energy in a hospital has two properties: it never stops, and when it does the cost is not measured in money. For theatres, intensive care and laboratories, continuity is an obligation rather than a comfort.

Get in touch

Continuity

What happens in the seconds after a failure?

Backup power in a hospital works in two stages. The UPS covers the first seconds, the generator takes over within tens of seconds. If any link in that chain fails, the gap shows up in a theatre or an intensive care unit.

Whether the chain is ready can only be known through continuous monitoring. Battery health, transfer switch state, generator heater and fuel level belong together; if one is missing, the chain is incomplete.

  • UPS battery health and transfer records
  • Generator readiness and automatic transfer state
  • Voltage and interruption records on critical boards

Every test and every real transfer is logged. When an inspection asks whether the backup system works, the answer is a record list rather than a statement.

Generator Readiness

continuous measurement
refill threshold 50%

68%

Eighteen hours at full load, with theatre and ICU circuits taking priority.

  • last refill · 2 Aug
  • load test · 19 Aug
1,360L
kalan
18h
tam yükte
Schematic: level, tests and refills on one axis. A widening gap between tests raises a reminder.

Outage anatomy

What did those seconds do to each circuit?

The question after an outage is always the same: which circuit went dark, and for how long? That can only be answered if the moment itself was recorded second by second.

The panel holds the loss of grid supply, the UPS pick-up and the instant the generator took load on one shared time axis. Each circuit sits in its own band, with the dark interval marked on it.

  • Grid loss and restoration recorded to the millisecond
  • Outage duration held separately for each critical circuit
  • The record goes straight into audits and incident reports

On UPS-backed circuits the interruption is measured in milliseconds and is never felt. Circuits fed by the generator alone stay dark for the transfer time, and knowing that number is the first condition for deciding which equipment belongs on which circuit.

Outage Record

14 August · 03:41
Grid lost0 ms UPS carrying20 ms Generator on load18 s Grid restored47 s
  • Theatres UPS + gen. kesintisiz
  • Intensive care UPS + gen. kesintisiz
  • Imaging Generator 18 s
  • Laboratories Generator 18 s
  • Administration Grid 47 s
Schematic: UPS-backed circuits never see the outage; generator-fed circuits stay dark for the transfer time.

Climate

Heating and cooling run all year

In most buildings heating and cooling are seasonal. In a hospital both run continuously: theatres and intensive care hold fixed temperature and humidity, laboratories and pharmacies keep their own ranges, and patient rooms may call for heating at the same time.

That is why a hospital load profile is flat and high. The gap between day and night is far smaller than in other sectors, and savings come from running plant correctly rather than switching it off.

  • Theatre and ICU air handling units metered separately
  • Chiller plant and boiler house as their own lines
  • Dehumidification and fresh air load tracked apart

With both loads spread either side of one axis the real question becomes visible: why are both high in the shoulder season? The answer is usually simultaneous heating and cooling, or a fresh air rate that never changes.

Heating and Cooling

12 months · one axis
468 468 234 234 JanFebMarAprMayJunJulAugSepOctNovDec

Cooling Heating MWh both running high · Apr, Oct

Schematic: cooling above the zero line, heating below. Months where both rise point at systems running at the same time.

Critical circuits

Which circuit is fed from which source?

Not every board in a hospital carries the same weight. Theatre and intensive care boards are fed from both UPS and generator; administrative areas run on the grid alone.

The panel keeps that hierarchy as it is. Which source feeds each circuit, what capacity that source has and where the current load sits against it are all on one screen.

  • Source and redundancy state per circuit
  • Capacity utilisation and remaining headroom
  • Interruption and voltage event records on critical circuits

Headroom matters most. When new equipment arrives, whether generator capacity still covers it is checked against measured load rather than a calculation on paper.

Critical Circuits

source and utilisation
CircuitSourceUtilisation %Load kW
TheatresUPS + generator 62 148
Intensive careUPS + generator 71 196
ImagingGenerator 84 240
LaboratoriesGenerator 48 92
AdministrationGrid 39 118
Schematic: as utilisation rises, headroom falls. This table is read before new equipment is added.

Which modules work in a hospital

Module What it does here
Standby Power UPS and generator readiness, test records, fuel tracking
Chillers and Cooling Year-round cooling load, air handling and pump efficiency
Power Quality Voltage events, harmonics and interruption records
Energy Consumption Block and department breakdown, critical circuit load
Remote Control Schedules in administrative areas, view-only on clinical circuits
Bill Validation Line-by-line checks across a multi-supply campus
AI Assistant Direct answers to “which block drifted this month”

Where control stops

Remote control is used far more narrowly in a hospital than in other sectors, and that is a deliberate choice. Clinical circuits, theatre and intensive care boards are marked view-only in the panel, and no command can reach them.

Control belongs in administrative areas, external lighting, car parks and grounds. There, schedules and rules take load off the facilities team; on the clinical side the panel’s job is only to watch and to report.

Let us measure what is happening on your site.

In a one-hour call we look at your existing setup and set out exactly which measurement points are needed and what you would be able to see.

Get in touch